Elevator Recall

coming soon

SCBA & SCUBA

National Fire Control offers hydrostatic testing services of most types of D.O.T. rated cylinders, both steel and aluminum. At our Kona facility, we have our high pressure hydrostatic testing lab where competent testing and safety are stressed. At our Maui, Kauai, and Oahu labs we can quickly turn-around low pressure cylinder testing with careful handling of cylinders as our top and most important consideration. Most cylinders can be tested and back in service in 2-3 working days. Our technicians are trained and certified to meet D.O.T. requirements and our facility is licensed, certified, and monitored by the U.S. Department of Transportation.

Hydrostatic testing is a nondestructive test required by the Department of Transportation to insure the integrity of pressurized cylinders. These include everything from small fire extinguishers, to Self Contained Breathing Apparatuses (SCBA) used by fire departments, to CO2 cylinders used for soft drinks, to medical and industrial oxygen cylinders, to Nitros cylinders used for race cars and SCUBA tanks used by divers.

Hydrostatic testing for different types of cylinders is required at different intervals.

All DOT-3AL marked CO2 cylinders are to be inspected and hydrostatically tested every five years as required in CFR Title 49 Part 180.205(c). Cylinders still with charge at the time the 5 year test is due, do not have to be tested until the charge is used, but prior to the re-filling of the cylinders.

High pressure, fiber wrapped aluminum cylinders, such as those used by fire fighters must be tested every three years and must be decommissioned after 15 years.

Additional information can be found in the Code of Federal Regulations (CFR) 49, under "transportation".

 Cylinder type

Testing Interval

 SCBA bottles, composite

 3 years (15 year life)

 SCBA bottles, carbon composites by Luxfer

5 years

 SCBA bottles, steel or aluminum

5 years

 Oxygen bottle, steel or aluminum

5 years

CO2 bottles

5 years

A/C bottle, 4BA bottle

5 years

 

 

 

 

 

 

 

 

 

 

 

 

NFPA 10 lists these guidelines for portable fire extinguishers.

 

 Extinguisher Type

Hydrostatic Testing Interval 

Stored Pressure Water, Loaded Stream, and/or Antifreeze fire extinguishers

5 Years

Wetting Agent fire extinguishers

5 Years

AFFF (Aqueous Film Forming Foam) fire extinguishers

5 Years

FFFP (Film Forming Fluoroprotein Foam) fire extinguishers

5 Years

Dry Chemical With Stainless Steel Shells fire extinguishers

5 Years

Carbon Dioxide fire extinguishers

5 Years

Dry Chemical, Stored Pressure, with mild steel shells, brazed grass shells, or aluminum shell fire extinguishers

12 Years

Dry Chemical, Cartridge or cylinder operated, with mild steel shell fire extinguishers

12 Years

Halogenated Agent fire extinguishers

12 Years

FE-36 fire extinguishers

12 Years

Dry Powder, Stored Pressure, Cartridge or Cylinder-Operated, with mild steel shell fire extinguishers

12 Years

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

First, the cylinders are visually inspected. Visual inspection, at the time of hydrostatic testing, must be performed by a DOT licensed test agency. Visual inspection must be performed in accordance with CGA pamphlet C-6.1; Standards for Visual Inspection of High Pressure Aluminum Compressed Gas Cylinders. Internal and external visual inspection of a cylinder is performed prior to hydrostatic testing.   The visual inspection includes:  checking for cracks and fissures, sidewall stamps, rust, and verifying the correct tolerances for outside diameter, wall thickness, length and straightness.

Next, the cylinders are put under pressures of over 66% higher than their normal working pressure.  Hydrostatic testing must be performed by a DOT licensed re-test agency. Hydrostatic testing must be performed in accordance with CGA Pamphlet C-1; Methods for Hydrostatic Testing of Compressed Gas Cylinders. 

Once a cylinder has successfully passed all visual inspection and hydrostatic test requirements, it is to be permanently marked with the test date, month and year, and licensed test agency's number in the proximity of the previous hydrostatic test date.  No cylinder is to be marked with the licensed test agency's number until the cylinder has passed all visual inspection and hydrostatic test requirements. No cylinder is to be marked with a licensed test agency number by any other person or agency other than the personnel of the licensed test agency.

Fire Hydrant

NFPA standards require that all public fire hydrants be inspected on a regular basis. Fire hydrants can be affected by a number of outside factors, including regular wear-and-tear, accidental damage, vandalism, mechanical function and even contractors who forget to turn them back on after a job. If your Hawaiian building's fire hydrant needs inspection, call National Fire Protection today. Our certified trained technicians can ensure that your fire hydrant stays up to code and will be able to protect you and your business in the event of a fire.

Fire Hydrant Inspection Process

At National Fire Protection, our fire hydrant inspection process is designed to ensure that your building's fire hydrant meets all proper codes. We start by opening your fire hydrant fully and letting it flow for at least a full minute. This clears all foreign material out of the fire hydrant and lets it run as smoothly as possible. After stopping the flow we observe the fire hydrant and make sure it drains properly. Finally, we lubricate all fire hydrant stems, threads and caps to make sure they are in proper operating condition and will be easily accessible to the fire department.

Fire Hydrant Inspection Precautions

Because of the dynamics of water, there are a number of things that must be taken into consideration when testing out a fire hydrant.

Water Hammer

Water hammer is caused by an abrupt stop of fast moving water. It usually occurs if a valve is shut down too quickly. The effect of fast moving water slamming into a valve is the same as the effect of a fast moving car slamming against a brick wall.

Since water is incompressible, it does not absorb any of the energy from a high velocity impact – instead, it transfers it to the system, pipes, hydrants and ground, which can lead to cracking and all out destruction of the fire hydrant. At National Fire Protection, we take care to keep your fire hydrants safe from water damage during inspection.

Brown Water

Brown water is caused by a sudden change in the amount of water in a water main, such as the increased water flow from opening a fire hydrant. When water starts flowing faster, it kicks up sediment that usually stays on the bottom of the pipes and moves it with the water. There is nothing harmful about the sediment in water pipes, and at National Fire Protection, we work hard to keep the brown water out of your faucets during our fire hydrant inspections.

Is your Hawaiian building's fire hydrant ready for inspection? Call National Fire Protection today to make sure your hydrant is up to code and able to protect you in the event of a fire.

Emergency/Exit Light

Exit/Emergency Lighting Regulations 

Did you know that you are required by law to have and test regularly exit & emergency lighting systems? Do not take a chance with such serious matters: avoid serious liabilities and fines by having, maintaining and testing adequate exit and emergency lighting systems in your building(s).

All lighting systems that we design and install rigorously adhere to the current lighting regulations and the best practices in your area. As for testing, rely on our exclusive, patented methodology of testing exit signs and emergency lighting systems - it is more affordable than you think, and it is the law!

Following are some lighting regulations on test and maintaining Exit & Emergency lighting systems:

OSHA Code of Federal Regulations
• Requires adequate and reliable illumination for all exits 
• Requires proper maintenance to assure that exit lighting is in continuously proper operating condition

NFPA 70 - National Electric Code
• Requires specific illumination and performance of emergency and exit lights 
• Provides functional standards for battery-powered emergency and exit lighting

NFPA 101 - Life Safety Code 
• Requires a monthly inspection of all emergency and exit lighting systems 
• Requires an annual test of all emergency and exit lighint systems

International Fire Code 
• Requires proper illumination of means of egress 
• Requires assurance that emergency and exit lighting systems will provide illumination for at least 60 minutes


NFPA 1997 5-9.3
Periodic Testing of Emergency Lighting 
Equipment
An annual test shall be conducted for a 1-1/2 hour duration. Equipment shall be fully functional for the duration of the test.


Standard Fire Prevention Code 1999
807.1.4 Exit Illumination and Signs 
A functional test shall be conducted on every required emergency lighting system at 30-day intervals for a minimum of
30-seconds.

 

SECTION 5-8 ILLUMINATION OF MEANS OF EGRESS

5-8.1 General.

5-8.1.1 Illumination of means of egress shall be provided in accordance with section 7.8 for every building and structure where required in Chapters 11 through 42. For the purposes of this requirement, exit access shall include only designated stairs, aisles, corridors, ramps, escalators, and passageways leading to an exit.

5-8.1.2 Illumination of means of egress shall be continuous during the time that the conditions of occupancy require that the means of egress be available for use. Artificial Lighting shall be employed at such places and for such periods of time as required to maintain the illumination to the minimum footcandle {Lux(lx)} values herein specified.

5-8.1.3* The floors of means of egress shall be illuminated at all points including angles and intersections of corridors and passageways, stairways, landings of stairs, and exit doors to values of not less than 1 footcandle (10 lx) measured at the floor. Exception: In assembly occupancies, the illumination of the floors of exit access shall be not less than 1/5 footcandle (2 lx) during periods of performances or projections involving directed light.

5-8.1.4 Any required illumination shall be so arranged that the failure of any single Lighting unit, such as the burning out of an electric bulb, will not leave any area in darkness.

 

 

SECTION 5-9 EMERGENCY Lighting


5-9.1 General.


5-9.1.1 Emergency Lighting facilities for means of egress shall be provided in accordance with this section for every building or structure where required in Chapters 8 through 30. For the purposes of this requirement, exit access shall include only designated stairs, aisles, corridors, ramps, escalators, and passageways leading to an exit.

5-9.1.2 Where maintenance of illumination depends upon changing from one energy source to another, there shall be no appreciable interruption of illumination during the changeover. Where emergency Lighting is provided by a prime mover-operated electric generator, a delay of not more than 10 seconds shall be permitted.

5-9.2 Performance of System.

5-9.2.1* Emergency illumination shall be provided for a period of 1 1/2 hours in the event of failure of normal Lighting. Emergency Lighting facilities shall be arranged to provide initial illumination that is no less than an average of 1 footcandle (10 lx) and a minimum at any point of .1 footcandle (1 lx) measured along the path of egress at floor level. Illumination levels may decline to .6 footcandle (6 lx) average and a minimum at any point of .06 footcandle (.6 lx) at the end of the emergency Lighting time duration. A maximum to minimum illumination uniformity ratio of 40 to 1 shall not be exceeded.

5-9.2.2* The emergency Lighting system shall be so arranged as to provide the required illumination automatically in the event of any interruption of normal Lighting, such as any failure of public utility or other outside electrical power supply, opening of a circuit breaker or fuse, or any manual act(s), including accidental opening of a switch controlling normal Lighting facilities.

5-9.2.3 Emergency generators used to provide power to emergency Lighting systems shall be installed, tested, and maintained in accordance with NFPA 110, Emergency and Standby Power Systems.

5-9.2.4* Battery-operated emergency lights shall use only reliable types of rechargeable batteries provided with suitable facilities for maintaining them in properly charged condition. Batteries used in such lights or units shall be approved for their intended use and shall comply with NFPA 70, National Electrical Code.®

5-9.2.5 The emergency Lighting system shall be either continuously in operation or capable of repeated automatic operation without manual intervention.

5-9.3 Testing and Maintenance.

 

 

SECTION 5-10 MARKING OF MEANS OF EGRESS


5-10.1 General.


5-10.1.1 Means of egress shall be marked in accordance with this section where required in Chapters 8 through 30.

5-10.1.2* Exits shall be marked by an approved sign readily visible from any direction of exit access.
Exception: Main exterior exit doors that obviously and clearly are identifiable as exits.

5-10.1.3 Access to exits shall be marked by approved readily visible signs in all cases where the exit or way to reach it is not readily apparent to the occupants. Sign placement shall be such that no point in the exit access is more than 100 ft (30 m) from the nearest visible sign.

5-10.1.4* Where floor proximity exit signs are specifically required by Chapters 8 through 30, exit signs shall be placed near the floor level in addition to those signs required for doors or corridors by 5-10.1.2 and 5-10.1.3. These signs shall be sized and illuminated in accordance with the requirements of 5-10.2 and 5-10.3. The bottom of the sign shall be not less than 6 in. (15.2 cm) nor more than 8 in. (20.3 cm) above the floor. For exit doors, the sign shall be mounted on the door or adjacent to the door with the closest edge of the sign within 4 in.(10.2cm) of the door frame.

5-10.1.5* Every sign required by Section 5-10 shall be so
located and of such size, distinctive color, and design as to be readily visible and shall provide contrast with decorations, interior finish, or other signs. No decorations, furnishings, or equipment that impair visibility of an exit sign shall be permitted, nor shall there be any brightly illuminated sign (for other than exit purposes), display, or object in or near the line of vision of the required exit sign of such a character as to so detract attention from the exit sign.

5-10.1.6 Where floor proximity egress path marking is specifically required by Chapters 8 through 30, a listed and approved floor proximity egress path marking system that is internally illuminated shall be installed within 8 in. (20.3 cm) of the floor. The system shall provide a visible delineation of the path of travel along the designated exit access and shall be essentially continuous, except as interrupted by doorways, hallways, corridors, or other such architectural features. The system shall operate continuously or at any time the building fire alarm system is activated. The activation, duration, and continuity of operation of the system shall be in accordance with 5-9.2.

5-10.2* Size of Signs.

5-10.2.1 Externally illuminated signs required by 5-10.1 and 5-10.4.11 shall have the word “EXIT” or other appropriate wording in plainly legible letters not less than 6 in. (15.2 cm) high with the principal strokes of letters not less than 3/4 in. (1.9 cm) wide. The word “EXIT” shall have letters of a width not less than 2 in. (5 cm) except the letter “I,” and the minimum spacing between letters shall be not less than 3/8 in. (1 cm). Signs larger than the minimum established in this paragraph shall have letter widths, strokes, and spacing in proportion to their height.

5-10.2.2 Internally illuminated signs required by 5-10.1 and 5-10.4.1.1 shall have the word “EXIT” or other appropriate wording in letters legible from a distance of at least 100 ft (30 m) under all normal and emergency Lighting conditions (30 fc and 1 fc, respectively). Internally illuminated signs shall be listed in accordance with UL 924.

5-10.3 Illumination of Signs.

5-10.3.1* Every sign required by 5-10.1.2 or 5-10.1.3 shall be suitably illuminated by a reliable light source. Externally and internally illuminated signs shall be visible in both the normal and emergency Lighting mode.

5-10.3.2* Externally illuminated signs shall be illuminated by not less than 5 footcandles (54 lx) and shall employ a contrast ratio of not less than 0.5.

5-10.4 Specific Requirements.

5-10.4.1 Directional Signs.

5-10.4.1.1* A sign complying with 5-10.2 reading “EXIT” or a similar designation with a directional indicator showing the direction of travel shall be placed in every location where the direction of travel to reach the nearest exit is not apparent. Directional signs shall be listed.

5-10.4.2* Special Signs. Any door, passage, or stairway that is neither an exit nor a way of exit access and that is so located or arranged that it is likely to be mistaken for an exit shall be identified by a sign reading “NO EXIT.” Such sign shall have the word “NO” in letters 2 in. (5 cm) high with stroke width of 3/8 in. (1 cm) and the word EXIT in letters 1 in. (2.5 cm) high, with the word EXIT below the word NO.
Exception: Approved existing signs.
Figure 5-10.4.1.2

 

 

SECTION 31-1 OPERATING FEATURES, GEN. REQUIREMENTS


31-1.3.7 Periodic Testing of Emergency Lighting Equipment. A functional test shall be conducted on every required emergency Lighting system at 30-day intervals for a minimum of 30 seconds. An annual test shall be conducted for the 1 1/2 hour duration of the test. Written records of visual inspections and tests shall be kept by the owner for inspection by the authority having jurisdiction.

Exception: Self-testing/self-diagnostic, battery-operated emergency Lighting equipment that automatically performs a minimum 30-second test and diagnostic routine at least once every 30 days and indicates failures by a status indicator shall be exempt from the 30-day functional test, provided a visual inspection is performed at 30-day intervals.

Building Standpipe

National Fire Protection Inc. has been providing standpipe inspections for Hawaiian home/business owners for over 20 years. Standpipes are a critical component of any fire suppression system and we offer reliable and effective testing, repair and installation services to ensure that you are protected in the event of a fire emergency.

We are a full service fire protection service company and we meet all state and local Fire Department requirements. National Fire Protection Inc. has skilled and experienced technicians who are licensed by the local island fire departments

Standpipe System Requirements

Certified technicians at National Fire Protection Inc. will inspect, test, repair and install standpipe systems in compliance with all of the regulations prescribed by the National Fire Protection Association (NFPA) and each island fire code regulations.

The NFPA fire code requires inspection, testing and maintenance of standpipe systems and fire sprinklers. Our services meet these regulations in order to confirm that all systems are functioning in proper conditions.

Standpipe Inspecting, Testing and Maintenance

A standpipe is a system of pipes that is dry or holds water in order to fight a fire. The taller the building, the more water and pressure has to be pumped up the standpipe.

The services that National Fire Protection Inc. technicians perform on your standpipes and fire sprinklers meet all regulatory standards of the state and local fire departments. Through our services, we will make sure that all standpipe systems receive the following tests:

  • Air Tests
  • Hydrostatic Tests
  • Flow Tests
  • Gauge Tests
  • On-site Water Supply

We will test and inspect Class I and III standpipes as well as Class II (Wet) Standpipes. Our services will test for sway bracing, hangers and corrosion to insure that the system is in proper working condition.

At National Fire Protection Inc. we have a knowledgeable and experienced staff of technicians who will perform various services for your fire protection system needs. One of the oldest and most effective systems extinguishing fire is a standpipe system. It is mandatory to have your standpipe system inspected, tested and repaired and National Fire has all the resources and technical skills to perform these services for you.

banner-bottom

GSA

EMAIL US TO LEARN MORE ABOUT GSA SCHEDULE 84 »

  • logo1
  • logo2
  • logo3
  • logo4